Sizing the Solar Array for a 48V 314Ah (16 kWh) Battery Bank with a 5 kW Deye Single‑Phase Inverter
System Overview
Battery: 48V 314Ah → 16 kWh usable storage (assuming 100% DoD, though in practice we recommend 80–90% for cycle life).
Inverter: Deye 5 kW (single‑phase), continuous AC output.
Solar panels: 500 W each (monocrystalline or polycrystalline).
Key Assumptions & Real‑World Factors
Factor Value Used
Peak sun hours (daily average, Romania) 3.5–4.0 h (spring/summer average; winter is lower ~2–2.5 h)
System losses (wiring, dust, temperature, inverter, MPPT mismatch) 20–25% total
Battery charge efficiency (LiFePO₄) ~95%
Inverter efficiency ~95%
Daily desired autonomy 1 full cycle (charge from ~20% to 100% daily)
Step 1 – Energy required from solar per day
To fully charge a 16 kWh battery from 20% to 100%:
Usable charge needed = 16 kWh × 0.8 = 12.8 kWh (into battery)
Account for battery + inverter losses:
12.8 kWh ÷ (0.95 × 0.95) ≈ 14.2 kWh (DC energy needed from panels)
Step 2 – Solar array size (DC peak power)
Using Romania’s average of 3.8 peak sun hours (including seasonal variation):
Required array power = 14.2 kWh ÷ 3.8 h = 3.74 kWp
With 25% total system losses:
Required = 3.74 ÷ 0.75 ≈ 5.0 kWp
Step 3 – Number of 500 W panels
Panels needed = 5,000 W ÷ 500 W = 10 panels
Final Recommendation
Configuration Value
Number of 500 W panels 10 (minimum)
Total array size 5.0 kWp
String layout (for Deye 5 kW, single MPPT typical) e.g., 2 strings × 5 panels (if VoC allows) – check inverter max DC input voltage (usually ~450–500 V)
Daily estimated charge time ~4–5 hours of good sun to fully recharge from 20%
Important Practical Notes
Seasonality – In Romanian winters, you may get only 2–2.5 peak sun hours. For year‑round full daily cycling, consider increasing to 12–14 panels (6–7 kWp) to cover cloudy/winter days.
Over‑paneling – The Deye 5 kW inverter can often accept up to ~6.5–7 kWp of DC (check the spec for max PV input power). Over‑paneling helps on low‑sun days without harming the inverter.
Tilt & orientation – Optimise for south‑facing with a 30–40° tilt for maximum annual yield in Romania.
Battery protection – We recommend setting the Deye’s charge/discharge limits to keep the battery between 20% and 95% for longer lifespan.
Final Suggestion for Romania
For reliable daily operation (spring–autumn): 10 × 500W panels = 5 kWp
For winter resilience or off‑grid confidence: 12–14 panels (6–7 kWp), with the inverter’s max PV input verified.
Let me know if you need the exact string sizing (VoC, Vmp, current) based on your panel spec – I can run that for you.